Remotely located sites with non-combustible,Type I or II, Group B, F, S and U buildings having an individualbuilding total floor area not exceeding 1,000 m2 (10,764 ft2) shallbe permitted to omit a fire water system if the buildings have aNFPA 13 fire sprinkler system with a 60 minute water supply,manual and automatic NFPA 72 fire alarm system and have abuilding-to-building separation distance of at least 6.1 meters(20 feet). Remotely located sites shall not apply to buildingswithin or on the boundary of a community or a plant.
Remotely located sites with non-combustible,<br>Type I or II, Group B, F, S and U buildings having an individual<br>building total floor area not exceeding 1,000 m2 (10,764 ft2) shall<br>be permitted to omit a fire water system if the buildings have a<br>NFPA 13 fire sprinkler system with a 60 minute water supply,<br>manual and automatic NFPA 72 fire alarm system and have a<br>building-to-building separation distance of at least 6.1 meters<br>(20 feet). Remotely located sites shall not apply to buildings<br>within or on the boundary of a community or a plant.